Chill Experts HVAC

Call Directions

Chill Experts HVAC HVAC Solutions💡 Mastering the cold is an art🌬️
❄️ Experts in chilled water systems
⚙️ Engineering Comfort🛠️ Technical Mindset

🔧 CARRIER CHILLER COMMISSIONING | HVAC FIELD SERVICETMF CARRIER 🚀 A new generation of performance, reliability and energ...
29/10/2026

🔧 CARRIER CHILLER COMMISSIONING | HVAC FIELD SERVICE

TMF CARRIER

🚀 A new generation of performance, reliability and energy efficiency!
Proud to carry out the commissioning of a brand-new Carrier chiller, featuring advanced technology and variable-speed drive control, designed to deliver high performance, reliable operation and optimized energy consumption.

✅ Commissioning & Technical Checks:
Inspection and verification of all safety devices and protection systems.
Electrical terminal inspection, tightening and cleaning.
Refrigerant circuit evacuation using a vacuum pump, followed by refrigerant charging in accordance with the manufacturer's specifications.
Hydraulic circuit purging and pressure verification.
Startup, operating parameter measurements and comprehensive functional checks.
Performance monitoring to ensure stable and efficient operation.
⚙️ The result? Excellent operating performance, reliable system operation and promising energy efficiency.

A successful commissioning is not just about starting a machine — it is about ensuring safety, performance, reliability and long-term operational efficiency.

👏 Congratulations to Carrier for its continued innovation in HVAC technology!

28/10/2026

🔧 Preventive Maintenance and Operational Inspection of a CARRIER Rooftop Unit
Performed a preventive maintenance visit on a CARRIER rooftop HVAC unit to ensure reliable operation, equipment safety, and optimal system performance.
🔹 Maintenance Operations Performed:
Cleaning of air filters to maintain optimal airflow and minimize pressure drop.
Cleaning of the electrical control panel and visual inspection of electrical components.
Dust removal and tightening of accessible electrical connections, in accordance with safety procedures.
Inspection of safety devices and protective components.
General inspection of the unit’s overall condition.
Restarting the unit and verifying proper operation after maintenance.
✅ Objective: Prevent unexpected breakdowns, optimize HVAC system performance, improve equipment reliability, and ensure safe and continuous operation.
Preventive maintenance plays a key role in extending equipment service life, maintaining energy efficiency, and ensuring reliable indoor climate control.

🔧 Preventive Maintenance and Operational Inspection of a CARRIER Rooftop UnitPerformed a preventive maintenance visit on...
28/10/2026

🔧 Preventive Maintenance and Operational Inspection of a CARRIER Rooftop Unit
Performed a preventive maintenance visit on a CARRIER rooftop HVAC unit to ensure reliable operation, equipment safety, and optimal system performance.
🔹 Maintenance Operations Performed:
Cleaning of air filters to maintain optimal airflow and minimize pressure drop.
Cleaning of the electrical control panel and visual inspection of electrical components.
Dust removal and tightening of accessible electrical connections, in accordance with safety procedures.
Inspection of safety devices and protective components.
General inspection of the unit’s overall condition.
Restarting the unit and verifying proper operation after maintenance.
✅ Objective: Prevent unexpected breakdowns, optimize HVAC system performance, improve equipment reliability, and ensure safe and continuous operation.
Preventive maintenance plays a key role in extending equipment service life, maintaining energy efficiency, and ensuring reliable indoor climate control.

🔧 Mise en service d’un groupe d’eau glacée Carrier | HVAC⚙️ Étapes principales de l’intervention :✅ Vérification des org...
27/10/2026

🔧 Mise en service d’un groupe d’eau glacée Carrier | HVAC

⚙️ Étapes principales de l’intervention :
✅ Vérification des organes de sécurité et des raccordements électriques.
✅ Contrôle du circuit frigorifique et de ses composants.
✅ Remplissage et mise en pression du circuit hydraulique.
✅ Vérification de l’étanchéité et contrôle des pressions.
✅ Démarrage du groupe, prise des mesures nécessaires (pressions, températures, intensités électriques et paramètres de fonctionnement), réglages et vérification des performances.
✅ Contrôle final du bon fonctionnement de l’installation.
🎯 Objectif : assurer un démarrage fiable, sécurisé et des performances optimales du système d’eau glacée.
❄️ HVAC | Chillers | Commissioning | Maintenance industrielle

TMF CARRIER

26/10/2026

ا🔧 Diagnostic and Preventive Maintenance – CARRIER Chillers
As part of the maintenance and performance optimization of HVAC systems, the following operations were carried out:
✅ Technical diagnostics and general inspection of the CARRIER chiller.
✅ Cleaning of condenser coils to optimize heat transfer and improve cooling efficiency.
✅ Cleaning and dust removal inside electrical control panels.
✅ Inspection and tightening of electrical connections where necessary.
✅ Inspection and functional testing of safety devices and protection systems.
✅ General inspection of system components to prevent breakdowns and ensure reliable operation.

🎯 Objective: Ensure optimal equipment performance, improve energy efficiency, prevent unexpected failures, and extend equipment service life.

❄️ HVAC | Preventive Maintenance | Industrial Refrigeration

22/10/2026

HVAC Maintenance Report
Equipment: Carrier Chilled Water Chiller
Intervention: Troubleshooting and Repair
Work Carried Out:
Inspected the chiller and diagnosed a fault in the variable frequency drive (VFD).
Identified a defective cooling fan in the VFD and replaced it with a new one.
Checked the electrical connections and related components.
Restarted the chiller and carried out functional tests to verify proper operation.
Result:
The faulty VFD cooling fan was replaced, and the chiller was returned to service. Functional tests were completed successfully, and the unit was operating normally at the time of inspection.

HVAC Maintenance ReportEquipment: Carrier Chilled Water ChillerIntervention: Troubleshooting and RepairWork Carried Out:...
22/10/2026

HVAC Maintenance Report
Equipment: Carrier Chilled Water Chiller
Intervention: Troubleshooting and Repair
Work Carried Out:
Inspected the chiller and diagnosed a fault in the variable frequency drive (VFD).
Identified a defective cooling fan in the VFD and replaced it with a new one.
Checked the electrical connections and related components.
Restarted the chiller and carried out functional tests to verify proper operation.
Result:
The faulty VFD cooling fan was replaced, and the chiller was returned to service. Functional tests were completed successfully, and the unit was operating normally at the time of inspection.

21/10/2026

🔧 Maintenance corrective HVAC | Pompe à chaleur Carrier
Intervention technique sur une pompe à chaleur Carrier présentant une défaillance électrique au niveau de ses deux compresseurs.
Principales opérations réalisées :
Diagnostic électrique et frigorifique de l’installation.
Remplacement des deux compresseurs.
Remplacement des deux filtres déshydrateurs.
Remplacement des deux contacteurs électriques.
Vidange de l’huile frigorifique.
Récupération et recharge du fluide frigorigène R410A.
Vérification des organes de sécurité.
Remise en service et contrôle du fonctionnement de l’équipement.
✅ Objectif : rétablir les conditions normales de fonctionnement de l’installation et assurer la fiabilité de ses composants électriques et frigorifiques.

🔧 Maintenance corrective HVAC | Pompe à chaleur CarrierIntervention technique sur une pompe à chaleur Carrier présentant...
21/10/2026

🔧 Maintenance corrective HVAC | Pompe à chaleur Carrier
Intervention technique sur une pompe à chaleur Carrier présentant une défaillance électrique au niveau de ses deux compresseurs.
Principales opérations réalisées :
Diagnostic électrique et frigorifique de l’installation.
Remplacement des deux compresseurs.
Remplacement des deux filtres déshydrateurs.
Remplacement des deux contacteurs électriques.
Vidange de l’huile frigorifique.
Récupération et recharge du fluide frigorigène R410A.
Vérification des organes de sécurité.
Remise en service et contrôle du fonctionnement de l’équipement.
✅ Objectif : rétablir les conditions normales de fonctionnement de l’installation et assurer la fiabilité de ses composants électriques et frigorifiques.

20/10/2026

🔧 HVAC Service Intervention – Carrier Chiller Repair
I had the opportunity to participate in a corrective maintenance intervention on a Carrier 30HXC190 water-cooled chiller, alongside the TMF Services – Carrier service team.
🔍 Diagnosis: An internal leak in the condenser between the refrigerant circuit and the water circuit, causing significant system malfunctions.
🛠️ Work Performed:
Replacement of the defective condenser.
Compressor inspection and overhaul.
Specialized cleaning of the evaporator.
Complete cleaning of the refrigeration circuit.
Complete oil draining and replacement.
Replacement of filters and defective safety components responsible for the malfunction.
👏 A challenging technical intervention successfully carried out through teamwork, technical expertise, and professional collaboration with the TMF Services – Carrier service team.
Great teamwork, technical expertise, and professional commitment! 💪❄️

Address

Tunis
Tunis

Opening Hours

Monday 09:00 - 17:00
Tuesday 09:00 - 17:00
Wednesday 09:00 - 17:00
Thursday 09:00 - 17:00
Friday 09:00 - 17:00
Sunday 09:00 - 17:00

Telephone

55114085

Website

Alerts

Be the first to know and let us send you an email when Chill Experts HVAC posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Shortcuts

Share